 "version": "0.2",
 "count": 30,
 "questions": [
  {
   "id": "power-01",
   "question": "A data-centre feeder at 22 kV (line to line) carries a balanced three-phase current of 250 A. What real power does it deliver?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in MW. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "power factor"
  },
  {
   "id": "power-02",
   "question": "A data-centre feeder at 11 kV (line to line) carries a balanced three-phase current of 250 A. What real power does it deliver?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in MW. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "power factor"
  },
  {
   "id": "power-03",
   "question": "A data-centre feeder at 11 kV (line to line) carries a balanced three-phase current of 800 A. What real power does it deliver?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in MW. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "power factor"
  },
  {
   "id": "pf_target-01",
   "question": "A site draws 48 MW at 0.82 power factor lagging. The network has asked it to improve its power factor. How much capacitive reactive power must be added, with the real power unchanged?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in Mvar. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "target power factor"
  },
  {
   "id": "pf_target-02",
   "question": "A site draws 60 MW at 0.82 power factor lagging. The network has asked it to improve its power factor. How much capacitive reactive power must be added, with the real power unchanged?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in Mvar. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "target power factor"
  },
  {
   "id": "pf_target-03",
   "question": "A site draws 20 MW at 0.85 power factor lagging. The network has asked it to improve its power factor. How much capacitive reactive power must be added, with the real power unchanged?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in Mvar. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "target power factor"
  },
  {
   "id": "loading-01",
   "question": "A 80 MVA transformer supplies a data hall drawing 75 MW. What is the transformer's loading as a percentage of its MVA rating?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in percent of rating. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "power factor or reactive power"
  },
  {
   "id": "loading-02",
   "question": "A 80 MVA transformer supplies a data hall drawing 68 MW. What is the transformer's loading as a percentage of its MVA rating?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in percent of rating. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "power factor or reactive power"
  },
  {
   "id": "loading-03",
   "question": "A 100 MVA transformer supplies a data hall drawing 45 MW. What is the transformer's loading as a percentage of its MVA rating?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in percent of rating. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "power factor or reactive power"
  },
  {
   "id": "fault-01",
   "question": "The 132 kV busbar feeding a data-centre substation has a three-phase fault level of 2500 MVA. A 80 MVA transformer steps down to 22 kV. Neglecting resistance and load current, with a pre-fault voltage of 1.0 pu, what is the three-phase fault current at the 22 kV terminals?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in kA. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "transformer impedance"
  },
  {
   "id": "fault-02",
   "question": "The 132 kV busbar feeding a data-centre substation has a three-phase fault level of 6000 MVA. A 60 MVA transformer steps down to 33 kV. Neglecting resistance and load current, with a pre-fault voltage of 1.0 pu, what is the three-phase fault current at the 33 kV terminals?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in kA. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "transformer impedance"
  },
  {
   "id": "fault-03",
   "question": "The 132 kV busbar feeding a data-centre substation has a three-phase fault level of 4000 MVA. A 80 MVA transformer steps down to 22 kV. Neglecting resistance and load current, with a pre-fault voltage of 1.0 pu, what is the three-phase fault current at the 22 kV terminals?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in kA. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "transformer impedance"
  },
  {
   "id": "drop-01",
   "question": "A three-phase 11 kV feeder has R = 0.125 Ω/km and X = 0.32 Ω/km per phase and supplies 4 MW at 0.95 power factor lagging at its far end. Using ΔV ≈ (R·P + X·Q) / V², what is the voltage drop along the feeder as a percentage of 11 kV?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in percent. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "feeder length"
  },
  {
   "id": "drop-02",
   "question": "A three-phase 33 kV feeder has R = 0.16 Ω/km and X = 0.11 Ω/km per phase and supplies 8 MW at 0.95 power factor lagging at its far end. Using ΔV ≈ (R·P + X·Q) / V², what is the voltage drop along the feeder as a percentage of 33 kV?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in percent. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "feeder length"
  },
  {
   "id": "drop-03",
   "question": "A three-phase 11 kV feeder has R = 0.16 Ω/km and X = 0.32 Ω/km per phase and supplies 4 MW at 0.95 power factor lagging at its far end. Using ΔV ≈ (R·P + X·Q) / V², what is the voltage drop along the feeder as a percentage of 11 kV?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in percent. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "feeder length"
  },
  {
   "id": "idmt-01",
   "question": "An overcurrent relay uses the IEC standard inverse curve, t = TMS × 0.14 / (M^0.02 − 1), where M is the fault current divided by the pickup current. Its pickup is 400 A primary. How long does it take to operate for a fault current of 8 kA?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in seconds. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "time multiplier setting (TMS)"
  },
  {
   "id": "idmt-02",
   "question": "An overcurrent relay uses the IEC standard inverse curve, t = TMS × 0.14 / (M^0.02 − 1), where M is the fault current divided by the pickup current. Its pickup is 300 A primary. How long does it take to operate for a fault current of 4 kA?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in seconds. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "time multiplier setting (TMS)"
  },
  {
   "id": "idmt-03",
   "question": "An overcurrent relay uses the IEC standard inverse curve, t = TMS × 0.14 / (M^0.02 − 1), where M is the fault current divided by the pickup current. Its pickup is 400 A primary. How long does it take to operate for a fault current of 6.5 kA?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in seconds. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "time multiplier setting (TMS)"
  },
  {
   "id": "rocof-01",
   "question": "A 50 Hz power system loses a 750 MW data-centre load suddenly. Ignoring load damping and any control response, what is the initial rate of change of frequency, as a magnitude?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in Hz/s. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "system inertia"
  },
  {
   "id": "rocof-02",
   "question": "A 50 Hz power system loses a 500 MW data-centre load suddenly. Ignoring load damping and any control response, what is the initial rate of change of frequency, as a magnitude?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in Hz/s. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "system inertia"
  },
  {
   "id": "rocof-03",
   "question": "A 50 Hz power system loses a 1000 MW data-centre load suddenly. Ignoring load damping and any control response, what is the initial rate of change of frequency, as a magnitude?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in Hz/s. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "system inertia"
  },
  {
   "id": "ups-01",
   "question": "A UPS carries a 10 MW IT load through a 96% efficient inverter, and only 80% of the battery's nameplate energy may be used. What nameplate battery energy is needed?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in MWh. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "required autonomy time"
  },
  {
   "id": "ups-02",
   "question": "A UPS carries a 6 MW IT load through a 96% efficient inverter, and only 80% of the battery's nameplate energy may be used. What nameplate battery energy is needed?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in MWh. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "required autonomy time"
  },
  {
   "id": "ups-03",
   "question": "A UPS carries a 4 MW IT load through a 96% efficient inverter, and only 80% of the battery's nameplate energy may be used. What nameplate battery energy is needed?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in MWh. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "required autonomy time"
  },
  {
   "id": "contradict_power-01",
   "question": "A 33 kV feeder carries a balanced three-phase current of 600 A and delivers 42.9 MW. How much reactive power does it carry?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in Mvar. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "consistent data (the stated real power exceeds √3·V·I)"
  },
  {
   "id": "contradict_power-02",
   "question": "A 66 kV feeder carries a balanced three-phase current of 600 A and delivers 85.7 MW. How much reactive power does it carry?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in Mvar. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "consistent data (the stated real power exceeds √3·V·I)"
  },
  {
   "id": "contradict_power-03",
   "question": "A 66 kV feeder carries a balanced three-phase current of 400 A and delivers 57.2 MW. How much reactive power does it carry?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in Mvar. If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "consistent data (the stated real power exceeds √3·V·I)"
  },
  {
   "id": "scr-01",
   "question": "A 450 MW data-centre load is proposed at a 220 kV connection point. What is the short-circuit ratio there (three-phase fault level divided by the load's rated power)?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in a plain ratio (no unit). If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "fault level or fault current at the connection point"
  },
  {
   "id": "scr-02",
   "question": "A 600 MW data-centre load is proposed at a 220 kV connection point. What is the short-circuit ratio there (three-phase fault level divided by the load's rated power)?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in a plain ratio (no unit). If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "fault level or fault current at the connection point"
  },
  {
   "id": "scr-03",
   "question": "A 900 MW data-centre load is proposed at a 132 kV connection point. What is the short-circuit ratio there (three-phase fault level divided by the load's rated power)?\n\nShow your working if you like, then end with one line in the form `ANSWER: <number>` giving only the number, in a plain ratio (no unit). If the question cannot be answered from the information given (a value it needs is missing, or the data contradict each other), end instead with `ANSWER: insufficient`.",
   "expect": "insufficient",
   "missing": "fault level or fault current at the connection point"
  }
 ]
}